Switching element function PNP NO Rated operating distance sn 6 mm Installation non-flush Switching frequency f 0 ... 400 Hz Hysteresis H typ. 5 % Voltage drop Ud ≤ 2.5 V Operating current IL 0 ... 100 mA Off-state current I r 0 ... 0.5 mA typ. 0.1 µA at 25 °C No-load supply current I0 ≤ 15 mA Constant magnetic field B 200 mT Alternating magnetic field B 200 mT Degree of protection IP67 |
|
Compliance with standards and directives Standard conformity Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
Approvals and certificates UL approval cULus Listed, General Purpose |
Output polarity switched high
Assured operating distance sa 0 ... 4.86 mm
Reduction factor rAl 1
Reduction factor rCu 1
Reduction factor r304 1
Reduction factor rSt37 1
Nominal ratings
Operating voltage UB 10 ... 30 V DC
Reverse polarity protection reverse polarity protected
Short-circuit protection pulsing
Switching state indicator Multihole-LED, yellow
Functional safety related parameters
MTTFd 1010.5 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 3-pin
Housing material Brass, PTFE coated
Sensing face LCP , black
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V