Switching element function PNP NO Rated operating distance sn 4 mm Installation flush Switching frequency f 0 ... 2000 Hz Hysteresis H typ. 5 % Voltage drop Ud ≤ 3 V Rated insulation voltage UBIS 60 V Operating current IL 0 ... 200 mA Off-state current I r 0 ... 0.5 mA typ. 0.1 µA at 25 °C No-load supply current I0 ≤ 12 mA Switching state indication Multihole-LED, yellow |
|
Compliance with standards and directives Standard conformity Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
Approvals and certificates Protection class II Rated insulation voltage Ui 60 V Design-impulse-voltage withstand Uimp 800 V CCC marking because they do not require approval. |
Output polarity switched high
Assured operating distance sa 0 ... 3.24 mm
Reduction factor rAl 1
Reduction factor rCu 1
Reduction factor r304 1
Reduction factor rSt37 1
Nominal ratings
Operating voltage UB 10 ... 30 V DC
Reverse polarity protection reverse polarity protected
Short-circuit protection pulsing
Mag. Field strength, AC fields 200 mT
Mag. Field strength, DC fields 200 mT
Functional safety related parameters
MTTFd 1477 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Device connector M12 x 1 , 4-pin
Housing material Brass, PTFE coated
Sensing face Ryton R4
Protection degree IP67
Mass 23 g
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval Products with a maximum operating voltage of ≤36 V do not bear a