Switching element function PNP NO/NC Rated operating distance sn 40 mm Installation non-flush Actual operating distance sr 36 ... 44 mm Reduction factor rAl 0.31 Operating voltage UB 10 ... 30 V DC Switching frequency f 0 ... 180 Hz Hysteresis H typ. 5 % Reverse polarity protection reverse polarity protected Operating current IL 0 ... 200 mA Off-state current I r 0 ... 0.5 mA No-load supply current I0 ≤ 20 mA Time delay before availability tv 80 ms |
|
Compliance with standards and directives Standard conformity Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
Approvals and certificates EAC conformity TR CU 020/2011 Rated impulse withstand voltage Uimp 4000 V UL approval cULus Listed, General Purpose CCC approval CCC approval / marking not required for products rated ≤36 V |
Output polarity DC
Assured operating distance sa 0 ... 32.4 mm
Reduction factor rCu 0.3
Reduction factor r304 0.74
Reduction factor rBrass 0.39
Nominal ratings
Short-circuit protection pulsing
Voltage drop Ud ≤ 2 V
Operating voltage indicator LED, green
Switching state indicator LED, yellow
Functional safety related parameters
MTTFd 1230 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 4-pin
Housing material PA
Sensing face PA
Degree of protection IP69K
Protection class II
Rated insulation voltage Ui 253 V