Switching element function PNP NO Rated operating distance sn 4 mm Installation non-flush Switching frequency f 0 ... 1200 Hz Reverse polarity protection reverse polarity protected Repeat accuracy R ≤ 0.01 mm Operating current IL 0 ... 200 mA Off-state current I r 0 ... 0.5 mA typ. 0.1 µA at 25 °C No-load supply current I0 ≤ 17 mA Time delay before availability tv ≤ 8 ms Switching state indicator Multihole-LED, yellow Functional safety related parameters MTTFd 990 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 % Ambient conditions Ambient temperature -25 ... 70 °C (-13 ... 158 °F) Mechanical specifications Connection type Connector M12 x 1 , 4-pin Scope of delivery 2 self locking nuts in scope of delivery |
|
Compliance with standards and directives Standard conformity Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
Approvals and certificates EAC conformity TR CU 020/2011 CCC approval CCC approval / marking not required for products rated ≤36 V |
|
Dimensions |
Output polarity DC
Assured operating distance sa 0 ... 3.24 mm
Reduction factor rAl 0.5
Reduction factor rCu 0.4
Reduction factor r304 0.8
Hysteresis H typ. 5%
Nominal ratings
Operating voltage UB 10 ... 30 V
Short-circuit protection pulsing
Voltage drop Ud ≤ 3 V
Housing material brass, nickel-plated
Sensing face PBT
Degree of protection IP67
General information
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose