Switching element function PNP NC Rated operating distance sn 4 mm Installation flush Operating voltage UB 10 ... 30 V Switching frequency f 0 ... 500 Hz Hysteresis H typ. 5% Reverse polarity protection reverse polarity protected Operating current IL 0 ... 150 mA Off-state current I r 0 ... 0.5 mA typ. 0.1 µA at 25 °C No-load supply current I0 ≤ 15 mA Time delay before availability tv ≤ 20 ms |
|
Compliance with standards and directives Standard conformity Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 |
|
Approvals and certificates UL approval cULus Listed, General Purpose |
Output polarity DC
Assured operating distance sa 0 ... 3.24 mm
Reduction factor rAl 0.45
Reduction factor rCu 0.35
Reduction factor r304 0.7
Nominal ratings
Short-circuit protection pulsing
Voltage drop Ud ≤ 3 V
Switching state indicator Multihole-LED, yellow
Functional safety related parameters
MTTFd 1770 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 4-pin
Housing material brass, nickel-plated
Sensing face PBT
Degree of protection IP67
Mass 30 g
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V